KD-LK: Sectional module with two SF6 load break switches

Application:

Sectionalization of two busbar sections.

Standard equipment:

 2 three-phase load break switches RV44, class 徘 according to IEC 60265.1, SF6 insulation
 low voltage compartment
 door interlock

Options:

 panel for capacitive voltage detectors
 block contacts on load break switch 1 and/or 2
 load break switch turnkey lock
 key interlock on load break switch 1 and/or 2
 key interlock on both switches
 no door interlock
 motor operation: 24-48-110 V AC/DC, 220 V AC
 capacitive voltage detectors
 socle 200 mm, 300 mm or 400 mm (other dimensions on request)
 floor pans
 start buttons for load break switch 1 and/or 2
 remote control for load break switch 1 and/or 2

Specifications:

 

 

Rated voltage

 

 

 

kV

 

 

 

12

 

 

 

17.5

 

 

 

24

 

 

 

Rated current

 

 

 

 

 

 

800-1250

 

 

 

800-1250

 

 

 

800

 

 

 

Short circuit current

 

 

 

kA

 

 

 

25

 

 

 

25

 

 

 

20

 

 

 

Duration of the short circuit

 

 

 

sec

 

 

 

1

 

 

 

1

 

 

 

1

 

 

 

Module dimensions:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

 

 

 

mm

 

 

 

750

 

 

 

750

 

 

 

750

 

 

 

Depth

 

 

 

mm

 

 

 

1050 (*)

 

 

 

1050 (*)

 

 

 

1050 (*)

 

 

 

Height

 

 

 

mm

 

 

 

1700

 

 

 

1700

 

 

 

1700

 

 

 

Weight

 

 

 

kg

 

 

 

245

 

 

 

245

 

 

 

245