KD-AV: Voltage measuring transformer module

Application:

Positioning of the voltage measuring transformers.

Standard equipment:

 three-phase load break switch RV44, class 徘 according to IEC 60265.1, SF6 insulation
 2 interlocked earthing switches
 fuse holders
 fuses
 door interlock
 panel for capacitive voltage detectors
 low voltage compartment

Options:

 block contacts on load break switch
 block contacts on earthing switch
 load break switch turnkey lock
 key interlock on load break switch
 key interlock on both switches
 no door interlock
 motor operation: 24-48-110 V AC/DC, 220 V AC
 set of two or three voltage measuring transformers
 capacitive voltage detectors
 socle 200 mm, 300 mm or 400 mm (other dimensions on request)
 start button for load break switch
 remote control for load break switch

Specifications:

 

Rated voltage

kV

12

17.5

24

Rated current

6,3

6,3

6,3

Short circuit current

kA

 

 

25

25

20

Duration of the short circuit

 

 

sec

1

1

1

Module dimensions:  

 

 

 

 

 

 

Width

mm

 

 

500

500

500

Depth

mm

 

 

1050 (*)

1050 (*)

1050 (*)

Height

mm

 

 

1700

1700

1700

Fuse size

 

 

mm

 

 

292

292

292

Module weight (without voltage transformers)

 

 

kg

210 (**)

210 (**)

210 (**)

*Safe distance between the cubicle rear wall and the room wall is 150 mm min.